E1VVS 4X 95 #D

Description

Description

Standards

  • Product
    IEC 60502-1
  • Test
    IEC 60332-1
  • National
    ELOT 843

Electric cable with copper solid or stranded conductors with PVC insulation and PVC outer sheath.

 

Application

fixed installations in dry or wet places

 

Cable construction

1. copper conductor

2. PVC insulation

3. PVC outer sheath

 Note: upon request the cable could be manufactured with higher fire retardant performance to meet the standards BS/EN 50266 cat C, IEC 60322-3-24 cat C

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Insulation
PVC
Outer sheath
PVC
Sheath colour
Black
Lead free
Yes
Type of conductor
S
Conductor flexibility
Stranded class 2
Conductor shape
Sector-shaped
With Green/Yellow core
No
With smaller neutral conductor
-

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
95 mm²
Phase Conductor Cross Section
95 mm²
Neutral conductor section (when smaller)
95 mm²
Ground conductor cross-section
- mm²
Nominal insulation thickness
1.6 mm
Nominal outer sheath thickness
2.2 mm
Nominal outer diameter
37.0 mm
Approximate weight
4083 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Max. DC resistance of the conductor at 20°C
0.193 Ohm/km
Permissible current rating when buried
270 A
Permissible current rating in open air
240 A
Voltage drop, 3 conductors
0.4 V/A.km
Voltage drop, single phase
- V/A.km

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Rigid
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C
Weather resistance
Very good

Resources

Resources

Documentation

xls — 0 B

Declaration of Performance

  • Declaration of Performance n� : 1000426-GRLA
  • Certification Date : 7/3/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0832
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close