YHKXS 6/10KV, 12/20KV, 18/30 KV
YHKXS 6/10KV, 12/20KV, 18/30 KV
XLPE Unarmored cable with copper conductor International code: YHKXS or N2XSY
Read moreYHKXS 1*500/50 12/20 KV NEW
Nexans ref. M5N4 001900 - Country ref. M5N4 1*500/50//POL-3
- Packaging: Cut to length (m)
- Conductor cross-section: 500 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 47.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*630/50 12/20 KV NEW
Nexans ref. M6N4 001155 - Country ref. M6N4 1*630/50//POL-3
- Packaging: Cut to length (m)
- Conductor cross-section: 630 mm²
- Nominal insulation thickness: 8.0 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 47.1 mm
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*630/95 6/10 KV
Nexans ref. M3N4 001631
- Packaging: Cut to length (m)
- Conductor cross-section: 630 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 95 mm²
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 48.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*120/16 12/20KV
Nexans ref. M5N4 011880 - Country ref. M5N4 1*120/16//POL-3
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 31.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*120/50 18/30KV
Nexans ref. M6N4 000160
- Conductor cross-section: 120 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 36.0 mm
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*150/25 12/20KV
Nexans ref. M5N4 000800 - Country ref. M5N4 1*150/25//POL-3
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 32.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*150/50 6/10KV
Nexans ref. M3N4 000521 - Country ref. M3N4 1*150/50//POL-3
- Conductor cross-section: 150 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 29.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*185/25 12/20KV
Nexans ref. M5N4 010800 - Country ref. M5N4 1*185/25//POL-3
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 34.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*185/50 6/10KV
Nexans ref. M3N4 000165 - Country ref. M3N4 1*185/50//POL-3
- Conductor cross-section: 185 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 30.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/16 12/20KV
Nexans ref. M5N4 011883 - Country ref. M5N4 1*240/16//POL-3
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 36.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/25 12/20KV
Nexans ref. M5N4 001883 - Country ref. M5N4 1*240/25//POL-3
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 37.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/25 6/10KV
Nexans ref. M3N4 000531
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 32.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/50 12/20KV
Nexans ref. M5N4 001885
- Packaging: Cut to length (m)
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 37.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/50 12/20KV
Nexans ref. M5N4 001882
- Packaging: Cut to length (m)
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 37.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/50 6/10KV
Nexans ref. M3N4 000530 - Country ref. M3N4 1*240/50//POL-3
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 33.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*240/50 6/10KV
Nexans ref. M3N4 000532
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.0 mm
- Nominal outer diameter: 33.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*300/50 12/20KV NEW
Nexans ref. M5N4 000571 - Country ref. M5N4 1*300/50//POL-3
- Packaging: Cut to length (m)
- Conductor cross-section: 300 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.2 mm
- Nominal outer diameter: 39.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*300/50 18/30KV NEW
Nexans ref. M6N4 000256 - Country ref. M6N4 1*300/50//POL-3
- Packaging: Cut to length (m)
- Conductor cross-section: 300 mm²
- Nominal insulation thickness: 8.0 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 44.0 mm
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*300/50 6/10KV
Nexans ref. M3N4 000374 - Country ref. M3N4 1*300/50//POL-3
- Packaging: Cut to length (m)
- Conductor cross-section: 300 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 35.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*35/16 12/20KV
Nexans ref. M5N4 000801 - Country ref. M5N4 1*35/16//POL-3
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 25.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*35/16 6/10KV
Nexans ref. M3N4 000900
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 21.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*400/50 12/20KV
Nexans ref. M5N4 001451
- Packaging: Cut to length (m)
- Conductor cross-section: 400 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 43.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*50/16 12/20KV
Nexans ref. M5N4 010801 - Country ref. M5N4 1*50/16//POL-3
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*500/50 18/30KV NEW
Nexans ref. M6N4 000155 - Country ref. M6N4 1*500/50//POL-3
- Packaging: Cut to length (m)
- Conductor cross-section: 500 mm²
- Nominal insulation thickness: 8.0 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 52.0 mm
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*500/50 18/30KV NEW
Nexans ref. M6N4 000157 - Country ref. M6N4 1*500/50//POL-3,
- Packaging: Cut to length (m)
- Conductor cross-section: 500 mm²
- Nominal insulation thickness: 8.0 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 51.0 mm
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*70/16 12/20KV
Nexans ref. M5N4 010802 - Country ref. M5N4 1*70/16//POL-3
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 28.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*70/16 6/10KV
Nexans ref. M3N4 001726
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.7 mm
- Nominal outer diameter: 23.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*70/25 12/20KV
Nexans ref. M5N4 010803 - Country ref. M5N4 1*70/25//POL-3
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 28.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*70/25 6/10KV
Nexans ref. M3N4 001724
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 1.7 mm
- Nominal outer diameter: 24.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*95/16 12/20KV
Nexans ref. M5N4 000156
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 1.9 mm
- Nominal outer diameter: 29.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*95/35 18/30KV
Nexans ref. M6N4 000643
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 8.0 mm
- Screen section: 35 mm²
- Nominal outer sheath thickness: 2.1 mm
- Nominal outer diameter: 34.0 mm
- Rated Voltage Uo/U (Um): 18 / 30 (36) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 1*95/35 6/10KV
Nexans ref. M3N4 000643 - Country ref. M3N4 1*95/35//POL-3
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 35 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal outer diameter: 26.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
YHKXS 3*240/25 6/10KV
Nexans ref. M3N4 000930 - Country ref. M3N4 3*240/25//POL-3
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 3.2 mm
- Nominal outer diameter: 68.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 8xD
- Bending factor when laying: 16 (xD)
YHKXS 3*240/50 6/10KV
Nexans ref. M3N4 000931 - Country ref. M3N4 3*240/50//POL-3
- Conductor cross-section: 240 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 50 mm²
- Nominal outer sheath thickness: 3.2 mm
- Nominal outer diameter: 68.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 8xD
- Bending factor when laying: 16 (xD)
YHKXS 3*35/25 6/10KV
Nexans ref. M3N4 020975 - Country ref. M3N4 3*35/25//POL-3
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 42.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 8xD
- Bending factor when laying: 16 (xD)
YHKXS 3*35/25 6/10KV CAT B
Nexans ref. M3N4 023126 - Country ref. M3N4 3*35/25//POL-2
- Conductor cross-section: 35 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.4 mm
- Nominal outer diameter: 43.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 8xD
- Bending factor when laying: 16 (xD)
YHKXS 3*50/16 12/20KV
Nexans ref. M5N4 700935
- Conductor cross-section: 50 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 2.8 mm
- Nominal outer diameter: 53.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 8xD
- Bending factor when laying: 20 (xD)
YHKXS 3*70/16 12/20KV
Nexans ref. M5N4 700936
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 2.9 mm
- Nominal outer diameter: 57.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 8xD
- Bending factor when laying: 20 (xD)
YHKXS 3*70/25 6/10KV
Nexans ref. M3N4 000975 - Country ref. M3N4 3*70/25//POL-3
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 48.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 8xD
- Bending factor when laying: 16 (xD)
YHKXS 3*70/25 6/10KV CAT B
Nexans ref. M3N4 023125 - Country ref. M3N4 3*70/25//POL-2
- Conductor cross-section: 70 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 25 mm²
- Nominal outer sheath thickness: 2.6 mm
- Nominal outer diameter: 49.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 8xD
- Bending factor when laying: 16 (xD)
YHKXS 3*95/16 12/20KV
Nexans ref. M5N4 700937
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 5.5 mm
- Screen section: 16 mm²
- Nominal outer sheath thickness: 3.0 mm
- Nominal outer diameter: 61.0 mm
- Rated Voltage Uo/U (Um): 12 / 20 (24) kV
- Cable flexibility: 8xD
- Bending factor when laying: 20 (xD)
YHKXS 3*95/95 6/10KV
Nexans ref. M3N4 010641 - Country ref. M3N4 3*95/95//POL-3
- Conductor cross-section: 95 mm²
- Nominal insulation thickness: 3.4 mm
- Screen section: 95 mm²
- Nominal outer sheath thickness: 2.7 mm
- Nominal outer diameter: 52.0 mm
- Rated Voltage Uo/U (Um): 6 / 10 (12) kV
- Cable flexibility: 10xD
- Bending factor when laying: 20 (xD)
Description
Description
Standards
-
ProductIEC 60502-2
-
TestIEC 60332-1-2
Application
Power use outdoor application, even wet.
Suitable for fixed installations at open air, in tube or canals and underground.
Max. Operation temperature: 90°
Max. Short circuit temperature : 250° (Max 5 s)
Construction
CU/SC/XLPE/SC/SC TAPE/CU WIRES/ low temp. PVC
1. Conductor:
Compacted Round conductor class 2
2. Insulation:
Extruded inner semi conductive layer, XLPE insulation and extruded outer semi conductive layer + Semi-conductive tape
3. Metallic screen layer:
Copper wires with open helix copper tape
4. Outer sheath:
Low Temperature PVC, Red or as per customer requirement
5. Marking:
By Inkjet
6. Packing:
Drums can be wooden or steel
TEST AT WORKS according to IEC 60502-2
Liban Cables will carry out these tests on all the lengths and tests certificates will be provided
Sample tests
- Check of the build - up and color coding of the cable
- Check of dimensions
Insulation : according to IEC 60502-2 Parag. 17.5.2
Metallic screen : according to IEC 60502-2 Parag. 17.7
Oversheath : according to IEC 60502-2 Parag. 17.5.3
- Hot Set Test for XLPE insulation according to IEC 60502-2 parag. 17.10
These tests will be carried out on one length of each size during each inspection .
Tests certificates will be provided by Liban Cables
Type tests
Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2.
These tests will be carried out on one length of the order.
Tests certificates will be provided by Liban Cables
DRAWING YnHKXS
Characteristics
Characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania